1. Introduction

Uninterruptible and viable power supply to every household is one of the main challenge Indian government has taken, especially in rural and remote places which due to difficult terrain or due to economic reasons not connected to the main power grid. In such locations, renewable energy sources like Photovoltaics (PV) and wind energy are gaining attention due to easy installation, higher energy utilization rate, lower power transmission loss and lower operational cost. However, unpredictable and inconsistent nature are major drawback of some of the renewable sources to provide viable power energy. To counter this different renewable and non-renewable sources can be integrated together for increased system efficiency, greater balance of energy and viable power supply (). However, selection of components of hybrid energy system and size optimization is very important to have reliable and cost effective system. The load demand and power generation with storage need to be optimally match, so that maximum utilization of energy sources and minimum investment can be assured. Various energy sources such as solar, wind, hydro, biomass and biogas etc. which are cost effective can be integrated together to meet viable electric load demand (). There are various advantages of IRES (i) better utilization of renewable energy (ii) better load matching (iii) better controllability (iv) less operational and maintenance cost (v) lesser environmental emission (; ).

Effective integration of hybrid energy sources has been gaining attention in the scientific community since past few decades to solve the technical and economic barriers for using renewable and distributed systems (; ; ; ; ; , ; ). The study by Taele et al. () shows that installation of small scale solar PV systems at communities in Lesotho prevented frequent breakdowns, avoided large fuel storage and reduced power losses. Patil et al. () compared off-grid electrification of seven villages of Uttarakhand, India by integrating four different renewable energy sources to meet electrical and cooking needs. Baghadi et al. () investigated the performance of hybrid PV-wind diesel battery system in Adrar climate of southern Algeria. The optimized system was able to meet 70% of energy demand by renewable PV-wind system and thereby reduced fossil fuel consumption. Singh et al. () examined technical and economic feasibility of hybrid hydrogen fuel cell and PV system to meet the energy demand of academic building at Bhopal, India. The analysis shows 3 kW hydrogen fuel cell with 5 kW of PV as most feasible system with minimum NPC and zero percentage energy shortage to meet load demand. Lau et al. () showed that integration of PV and diesel sources with battery can expressively reduce dependence on solely available diesel resource. Yilmaz and Selim () reviewed different design techniques of biomass to energy conversion and integration of different renewable sources with biomass. The study shows that with appropriate integration of renewable energy resources and technologies, load demand can be met efficiently. Rahman et al. () investigated technical and economic optimization of hybrid biomass and photovoltaic system to meet both thermal (cooking) and electric loads, replacing conventional facilities.

Ozden and Tari () studied exergy and energy analysis of hybrid solar-hydrogen system in Ankara, Turkey. The result shows that overall hybrid system efficiency and hydrogen cycle efficiency are 6.21% and 4.06% respectively. The authors also suggested that PV-hydrogen hybrid system is better than PV-battery system. Using inspired coevolutionary algorithm shi et al. () designed hybrid energy system with PV, wind turbines, batteries and diesel generator. The optimization of the system includes minimization of annualized cost of the system, loss of power supply probability and fuel usage. A multi-objective receding horizon optimization is proposed by Forough and Roshandel () to determine optimal scheduling of hybrid energy system. Diesel fuel cost and battery wear cost were considered as two objective functions. Castellanos et al. () studied various combination of PV, anaerobic digester and combined heat and power unit using micro-grid modelling simulations to power a small village in West Bengal, India. The result shows that IRES containing PV, anaerobic digester, and a micro turbine has lower capital and electricity cost over the life of the project. The design and evaluation of PV-hybrid systems by M. Muselli et al. () and M.R. Borges Neto et al. () analysed the optimal contribution of system components to serve the demand. Giatrakos et al. () presented sustainable planning of renewable based energy system by replacing existing diesel generator with hybrid PV-Wind and hydrogen system for Karpathas island of Dodecanese, Greece.

From the literature study, it has been observed that considerable work has been done on optimization of integrated system considering different configuration and optimization technique. However, most of the study did not optimize the system, considering seasonal variation in energy load demand. This is important for accurate designing of hybrid system to have maximum resource utilization with minimum system cost to meet load demand all time. Present study focus on size optimization and economic analysis of hybrid integrated renewable energy system with seasonal load demand. Mathematical modelling, feasibility study and control strategy of all the system component has been done. Also, sensitivity analysis of hybrid system with variation in system component cost has been carried out. The optimization of integrated system has been carried out using HOMER software.

The paper is organized as follows, Section 2 describes the proposed hybrid integrated renewable energy system. Section 3 explains specification and mathematical modeling of components of proposed IRES system and seasonal electric load demand. Section 4 explains methodology, constraints and control strategy implemented in present system. Section 5 discuss size, economic and energy analysis of optimized IRES configuration and section 6 discusses sensitivity analysis of system with variation in cost of system components.

2. Description of proposed IRES

The integrated energy system must be feasible and viable, i.e. at each time step some or the other energy system i.e. primary generation, backup system or storage system must be available to meet electric load demand. To achieve this, there are many possible configurations in which system components can be designed and integrated. Probabilistic approach of simulations of system components has been carried out for sizing based on wind speed, solar radiation, biogas specification, electric load demand and certain technical and physical parameter. The schematic of proposed IRES is shown in Figure 1. Different component of hybrid energy system includes wind turbine, solar PV, solar charge controller, inverter, battery, control panel, and biogas generator. In the present study, wind speed, solar radiation, ambient temperature, PV temperature, wind speed, fuel property of biogas and load reading are measured by various equipment and weather monitoring system available in the solar energy research laboratory at IIT Madras, India.

Figure 1 

Schematic of integrated hybrid renewable energy system.

For validation, modelling has been carried out similar to done by Baghdadi et al. () using HOMER software. The simulation and calculation shows similar results to those of Baghdadi et al.

3. Specification and Mathematical modeling of IRES components

3.1. Wind energy system

The power output of the wind turbine depends upon wind speed at the location and turbine specification and is calculated by Eq. (1) ().

(1)
Pwt=0Vt < VciPwt=Pr(Vr3Vci3)V3tVci3(Vr3Vci3)PrVciVt < VrPwt=PrVrVt < VcoPwt=0VtVco

Where V(t) is speed of wind at time t, Pr is wind turbine rated power and Vci, Vr, and Vco are respectively wind turbine cut in, rated and cut out speed ().

By knowing wind profile at reference height, wind speed at any other height can be calculated by Eq. (2).

(2)
Vh=VrefHHrα

Where Vh is wind speed at height H, Vref is wind speed at reference height Hr, and α is wind speed power law coefficient. The overall effective electrical power output of wind turbine (PWeff) can be expressed as Eq. (3).

(3)
PWeff= PwAwηwηinv

Where Aw is wind turbine swept area, ηw is wind turbine efficiency and ηinv is invertor’s efficiency. The wind speed for the complete year at height of 10 m above ground at IIT Madras, India is shown in Figure 2. The specification of wind turbine (Luminous Whisper 500) used for present study is summarized in Table 1.

Figure 2 

Wind speed profile at IIT Madras, India.

Table 1

Specification of wind turbine ().

ParameterUnitValue

Rated PowerkW3
Rated wind speedms–1 12
Cut-in wind speedms–1 3.1
Cut-out wind speedms–1 24
Rated voltageV240
Rotor diameterm4.5
Swept aream2 15.1

3.2. Solar photovoltaic system

The basic element of solar PV module is a solar cell that converts incident solar radiation directly into electrical energy (DC current) (; ). The power output of PV array depends upon PV module specification and is calculated by Eq. (4) ().

(4)
Ppv=NsNpVocISCFF

Where Np and Ns are respectively numbers of PV modules connected in parallel and series, Isc is short circuit current (A) of PV module, Voc is open-circuit voltage (V) of PV module, and FF is fill factor of panel.

The overall effective power from PV array is calculated by Eq. (5).

(5)
Par=ηmodηinvPpv

Where ηmod is PV module efficiency, ηinv is inventor efficiency.

The effects of solar irradiance at tilted PV (IT), solar irradiance coefficient (γc), average temperature of PV (TPV,avg), temperature coefficient (βc), efficiency of PV panel at standard test conditions (ηSTC) and area of PV (APV) on the electrical output (Epv) of the systems can be calculated by Eq. (6) ().

(6)
Epv=ηstc1+βcTpvavg25+γclnIT1000ITApv

The temperature of PV cell can be calculated by Eq. (7).

(7)
TPVavg=Tamb+(NOCT20)SmodSstc

Where Tamb is ambient temperature, NOCT is nominal operating cell temperature (°C), Smod is solar incident radiation (Wm–2) on the PV module and Sstc is incident solar radiation at standard test condition (Wm–2).

The power obtained from PV panel is directly related to the slope at which panel is installed. The maximum incident radiation on the solar panel for the given location is calculated by equation (8) ().

(8)
Smod=Sincsin90φ+δ+γ

Where declination angle δ is given by,

(9)
δ=23.45sin360/365284+ d

The yearly solar radiation at CRC building, IIT Madras is calculated and compared with the Indian Meteorological Department (IMD) solar radiation database (). The average hourly month wise solar radiation profile at CRC, IIT Madras is shown in Figure 3. The specification of PV (Bosch solar module CSi-P 60) used for present study is summarized in Table 2.

Figure 3 

Solar radiation profile at CRC building, IIT Madras, India (13.01°N, 80.24°E).

Table 2

Specification of PV module ().

ParametersValueParametersValue

Cell Configurations (Nos.)60Maximum System Voltage (DC)1000
Pmax (W) (Tolerance: +3%)250Series Fuse Rating (A)15
Voc (V) (Tolerance ±3%)37.00Nominal Operating Cell Temp. (°C)44.6
Isc (A) (Tolerance ±3%)8.55Temp. Coefficient of Pmax (%/°C)–0.45
Vmax (V) (Tolerance ±3%)30.95Temp. Coefficient of Voc (%/°C)–0.36
Imax (A) (Tolerance ±3%)8.08Temp. Coefficient of Isc (%/°C)0.043

3.3. Battery Bank system

The charging of battery takes place when power produced by wind turbine and PV is more than electric load demand. Battery bank is used to serve load demand when the power output of wind turbine and PV system is less than threshold value and is insufficient to meet load demand. Battery bank capacity is selected based on total power needed and autonomy period of operation in a day. The battery bank cost for complete duration of the project has three components: capital cost, operation & maintenance (O&M) cost, and replacement cost. The capital cost of battery bank depends on its size and specification, O&M cost includes maintenance cost at regular interval whereas replacement cost is cost of replacing battery after particular duration (lifetime). Thus selection of right battery bank is important during integration of system. The tabular lead acid batteries are largely used for solar application in India because of their low cost and robust usage. Thus, authors have considered tabular lead acid batteries for present analysis. The characterization of battery to know its charge and discharge status is determined by its state of charge (SOC). The SOC is defined as the ratio of current capacity to nominal capacity of the battery. When battery is fully charged, SOC is one and when the battery is empty, SOC is zero. The instantaneous SOC of battery can be calculated by Eq. (10) ().

(10)
SOC(t)=SOC(t1)1σΔt24+Ibat(t).Δt.ηbatCbat

Where SOC(t) is state of charge of battery at time t, SOC(t–1) is state of charge at (t–1) hours, σ is battery self-discharge rate, Ibat is battery current at time t (A), ηbat is battery charge efficiency and Cbat is capacity of battery bank.

The instantaneous battery current is given by Eq. (11) ().

(11)
Ibat(t)=Ppv(t)+Pw(t)Pload(t)Vbat(t)

Where Ppv(t) and Pw(t) are respectively instantaneous power generated by PV and wind turbine system, Pload(t) is instantaneous load demand and Vbat(t) is terminal voltage of battery bank. The capacity of the battery bank Cbat is given by Eq. (12) ().

(12)
Cbat=(ELoadAD)ηinvηbatDOD

Where Eload is total energy demand, AD is daily autonomy, DOD is depth of discharge of battery, ηinv is inventor efficiency, and ηbat is battery efficiency.

3.4. Biogas generator system

The biogas generator (Bio-Gen) is used as secondary power source for the proposed IRES system. The generator is used to meet peak load and when PV, wind turbine and battery power are insufficient to fulfill load demand. Biogas is used as fuel by biogas generator to produce electrical power. The biogas is produced by biodegradation of organic material fed into gasifier. The power output of biogas generator is given by Eq. (13) ().

(13)
Pbio= . CVBG . ηBG.ηgas3600

Where B is amount of biomass, CVBG is calorific value of biogas (kJ-kg–1), ηBG is efficiency of biogas generator and ηgas is efficiency of gasification of gasifier. The specification of generator considered for present study is listed in Table 3 ().

ParameterSpecification

ModelELEMAX SH5300EX Generator
Engine type4 stroke, single cylinder, side valve, Spark Ignition engine
Ignition systemTransistorized Coil Ignition (TCI)
Rated Power6.3 kW @ 3600 rpm
Generator AC output5.3 kVA @ 220 V, 60 Hz
Cooling systemForced Air Cooling

3.5. Converter system

Power converter is required to maintain flow of energy from different power sources of IRES to electric load by converting electric energy from one form to another (AC to DC and vice versa) (). The power generated by wind turbine, solar PV and power stored in battery bank is in DC form. Whereas, power generated by biogas generator and electric load is in AC form. Converter is a combination of both inverter (DC to AC) and rectifier (AC to DC), which operate as per the requirement of flow of energy ().

3.6. Load demand Profile

The electric load profile is the main influencing factor for designing and optimizing of integrated hybrid energy system. So, it is very important to know how load vary from weekdays to weekends and from season to season for accurate designing of hybrid system to have maximum utilization of resources and minimum system cost. The electric loads considered for present study are computers, fans, lights, electronic devices and machinery. The load demand of the building varies with weather condition. Chennai has three major seasons’ summer, monsoon and winter. March to August is summer season, September to October is monsoon season and November to February is winter season. The seasonal average electric load profile and frequency histogram of load for CRC building, IIT Madras is shown in Figure 4.

Figure 4 

Seasonal load demand at CRC, IIT Madras.

4. Optimization and Operational methodology

4.1. Component sizing and optimization

The optimization of integrated hybrid system has been done by HOMER software. The software simulates all possible system configurations to find the optimum combination of hybrid system to match seasonal electric load demand (). Various details like global solar radiation, ambient temperature, wind speed, specification of components, electric load demand are given as input for the simulation. The specification of system component and load demand of proposed IRES are described in section 3. The HOMER software determine various system combination in terms of economic and technical parameters. In present work optimization is done on the basis of net present cost of hybrid system.

4.1.1. Net present cost

The proposed optimisation process is based on lowest NPC of the system which is total of capital cost, O&M cost, replacement cost and salvage cost of the integrated system over the project life. The net present cost of the system calculated by HOMER is given by Eq. (14) ().

(14)
CNPC=CannCRF(i,Rproj)

Where Cann is annualized cost, CRF is capital recovery factor, i is annual real discount rate, Rproj is project lifetime (25 years).

4.1.2. Capital recovery factor

The capital recovery factor is ratio used to calculate present value of an annuity that is amount of cash flow annually over the lifetime of the project and is given by Eq. (15) ().

(15)
CRF(i,Rproj)=i(1+i)Rproj(1+i)Rproj1

Where i is nominal discount rate.

4.1.3. Cost of energy

The levelized cost of energy (COE) is average cost to generate per kWh of useful electrical energy by integrated system. It is one of the important economic assessment factor considered while optimizing integrated energy system. It is the ratio of total annualized cost (Cann) of system to useful energy served (Eser) by the system and is calculated by Eq. (16) ().

(16)
COE=CannEser

4.1.4. Salvage cost

Salvage cost (Csal) is value of the components of integrated system at the end of the project. The salvage cost is calculated by Eq. (17) ().

(17)
Csal=CrepRremRcomp

Where Crep is component’s replacement cost, Rrem is component’s remaining life, Rcomp is the lifetime of the project.

The real discount rate is used to convert between one-time cost and annualized cost and is calculated by Eq. (18) ().

(18)
i=if1+f

Where i’ is nominal discount rate and f is expected inflation rate.

Present operational strategy aim at maximizing wind and solar PV energy utilization and reducing operational duration of biogas generator and thereby reducing pollutant emission. Economic data and operation life of different components of integrated hybrid energy system are listed in Table 4.

Table 4

Economic data and operational life of components of IRES.

ComponentCapital cost (in $)O & M cost (in $)Replacement cost (in $)Life

Wind turbine1667/kW50/kW/year1667/kW25 year
Solar PV925/kW25/kW/year925/kW25 year
Solar inverter and control panel198/kW8/kW/year198/kW10 year
Battery (200 Ah, 12 V)153/batt7/batt/year125/batt5 year
Biogas-generator470/kW0.01/kWh380/kW20,000 h

4.2. Control strategy

The dispatch strategy for IRES is a control algorithm of interaction among various system components. The control operation is done on the basis of percentage of accurate load demand, wind turbine & PV power output and state of charge of battery. Figure 5 shows flow chart of operational stratergy of the system. Calculation of value these parameter is important to achieve optimum and viable operation. IRES systems involved in present study work in three modes (1) Wind turbine & Solar PV mode, (2) Battery bank mode, (3) Bio-generator mode. In proposed IRES wind turbine and solar PV are primary energy source because of zero fuel cost, low O&M, and zero emission. Whenever wind and PV energy is more than electric load demand excess energy is stored in the battery bank. When these energy sources are not sufficient to fulfill load demand, control algorithm checks if battery bank can fulfill the demand and if found above suitable SOC battery bank act as energy source. However, when battery bank is unable to supply the shortage biogas generator is used as last option with an aim to minimize emission of pollutants, operation, maintenance and fuel cost.

Figure 5 

Flow chart of operational strategy of proposed HRES.

5. Results and discussion

In the present section based on optimization strategy results of the proposed hybrid system are discussed based on optimal size, economic and energy output of the system.

5.1. Optimal sizing analysis of integrated system components

The effectiveness of optimization strategy in the proposed system is demonstrated by finding the contribution of individual components involved namely wind turbine, PV, battery, biogas generator and converter system. Maximum wind, PV and battery usage is adopted to meet the electric load demand. The HOMER software simulates 2358 solutions based on technical and economic parameters to find the optimal configuration, out of which 783 were feasible and 1575 were not feasible due to capacity constraint. The optimisation process is based on net present cost. Table 5 list some of the optimal feasible configurations of integrated hybrid renewable energy system. The combination are listed in descending order in terms of net present cost of the system. The most feasible configuration of IRES with minimum NPC and COE is combination of 12 kW solar Photovoltaics, 3 kW wind turbine, 15 kW biogas generator, 11 kW converter and energy storage back up with 40 battery (200 Ah, 12 V).

Table 5

Different configuration of some of the viable combination of integrated hybrid energy systems.

CombinationSolar PV (kW)Windturbine (kW)Bio-gen (kW)Battery (no.)Converter (kW)COE ($/kWh)Total NPC ($)Operating cost ($/yr)Initial capital ($)Bio-gen (kWh/yr)Solar PV (kWh/yr)Wind turbine (kWh/yr)Battery Autonomy (hr)Battery Usable Nominal Cap (kWh)

11231540110.090117098.16621.131503.951391.818708.21726.43.2724.02
21331540120.091117288.76558.332506.550153.420267.21726.43.2724.02
31431539110.091117305.46506.733190.149335.521826.31726.43.1923.42
41331540120.091117432.76561.632608.050086.320267.21726.43.2724.02
51431539120.091117592.46510.533427.349146.521826.31726.43.1923.42
61631539120.092117988.06404.135199.047195.024944.31726.43.1923.42
71631540120.092118195.46409.035342.847128.824944.31726.43.2724.02
81331540140.092118331.76600.733001.350086.320267.21726.43.2724.02
91531540160.094119761.66534.635284.948018.623385.31726.43.2724.02
101461539120.097122569.86520.038282.047624.821826.33452.83.1923.42
111461540120.097122596.56510.638430.647454.621826.33452.83.2724.02
121161540130.097122617.56711.435856.350830.517149.23452.83.2724.02
131561539120.098122980.36472.039313.646567.623385.33452.83.1923.42
141661539120.098123314.76426.340238.645647.524944.33452.83.1923.42
151191540110.103126981.26685.540553.649254.817149.25179.23.2724.02

5.2. Economic analysis of hybrid system

The optimisation process is based on net present cost which is total capital cost, O&M cost, replacement cost and salvage cost of all components of integrated system over the project life. The NPC and COE of the optimum IRES are $ 117,098 and $ 0.09 per kWh respectively. Table 6 lists net present cost breakdown analysis of optimum hybrid integrated energy system. It can be observed that the total cost of biogas system is maximum and account around 53% of total net present cost of the system followed by battery bank with 24%, solar PV with 13%, wind energy system with 5% and converter with 4%.

Table 6

Net present cost breakdown analysis of optimum hybrid integrated energy system.

ComponentPrincipal cost (in $)O & M cost (in $)Replacement cost (in $)Fuel cost (in $)Salvage cost (in $)Total ($)

Wind turbine5,000.001,939.130.000.000.006.939.13
Solar PV11,100.003,878.250.000.000.0014,478.25
Solar inverter and control panel2,233.941,166.841,973.550.00267.585,106.76
Battery6,120.003,619.7019,495.610.001,156.5628,078.75
Biogas-generator7,050.0010,073.7716,973.1928,589.51691.2761,995.19
Complete IRES31,503.9420,677.7038,442.3528,589.512,115.41117,098.09

5.3. Energy analysis of hybrid system

The total energy generated by integrated hybrid energy system in complete year is 71,826 kWh to supply AC primary load of 64,396 kWh per year. The energy output of 12 kW PV is 18,708 kWh/year with mean output of 51.3 kWh/day and has penetration factor of 29%. The energy output of wind turbine is 1,726 kwh/year and has penetration factor of 2.68%. The energy output of 15 kW biogas generator is 51,392 kWh/year with specific fuel consumption of 2.15 kg/kWh and mean electrical efficiency of 30.4%. The generator operate for 4,195 hours/year and has operational life of 4.85 years. The battery bank has autonomy of 3.27 hours with 11,486 kWh energy input, 9,198 kWh of energy output and 2,298 kWh of energy losses for a year. The expected life of battery is 4.11 years. The 11 kW inverter has capacity factor of 20.9% with 6,004 hours of operation in a year. The energy input, output and losses for inverter are 21,785 kWh, 20,695 kWh and 1,089 kWh for a year respectively. The 11 kW rectifier has capacity factor of 6.92% with 2,619 hours of operation in a year. The energy input, output and losses for rectifier are 7,204 kWh, 6,844 kWh and 360 kWh for a year respectively. The month wise percentage contribution of wind turbine, solar PV and biogas generator is shown in Figure 6.

Figure 6 

Monthly contribution of individual system components.

The hourly usage pattern of individual components is also important to know each components’ potential to satisfy load demand. Figure 7 shows power output of wind energy system on hourly basis for the complete year. The power output of wind turbine is related with wind speed and have more output during the month with higher wind speed. Figure 8 shows power output of PV system on hourly basis for the complete year. It can be observed that power generation is related to solar radiation intensity, during the sunny days power generation is more whereas there is decline during the rainy and winter days. Further, during the peak day time (11:00 am to 2:00 pm) the power generation by solar PV is more which is sufficient to meet load demand and excess power is stored in the battery bank. Figure 9 shows operational performance of battery bank on hourly basis. The battery bank life depend upon its charge and discharge cycle level. During the time when battery SOC reach below threshold level the biogas generator come in operation to meet the load demand. Figure 10 shows power output of biogas generator on hourly basis. The biogas generator operates for 2,304 hours in the complete year with 893 number of starts.

Figure 7 

Yearly Wind turbine output performance.

Figure 8 

Yearly PV output performance.

Figure 9 

Yearly battery bank performance.

Figure 10 

Yearly Bio-Gen output performance.

6. Sensitivity analysis of system

Sensitivity analysis is important as it helps us to predict the behavior of the system under different conditions. For the present hybrid renewable energy system sensitivity analysis has been done with variation of wind turbine cost, PV cost, battery cost, bio-gen cost.

6.1. Variation in wind turbine cost

The net present cost and cost of energy of the hybrid system has been evaluated by variation in wind turbine cost. The wind turbine cost has been varied from 0.8 to 1.3 times to its present capital cost. The NPC and CoE of the system varied from $ 116,108 to $ 118,608 and $ 0.088/kWh to $ 0.093/kWh respectively. The variation in NPC and CoE with change in wind turbine cost are shown in Figure 11.

Figure 11 

CoE and NPC analysis of hybrid system with variation in wind turbine cost.

6.2. Variation in PV cost

The net present cost and cost of energy of the hybrid system has been evaluated by variation in solar photovoltaic cost. The PV cost has been varied from 0.8 to 1.3 times to its present capital cost. The NPC and CoE of the system varied from $ 114,888 to $ 120,438 and $ 0.086/kWh to $ 0.097/kW/h respectively. The variation in NPC and CoE for change in PV cost are shown in Figure 12.

Figure 12 

CoE and NPC analysis of hybrid system with variation in PV cost.

6.3. Variation in battery cost

The net present cost and cost of energy of the hybrid system has been evaluated by variation in battery cost. The battery cost has been varied from 0.8 to 1.3 times to its present capital cost. The NPC and CoE of the system varied from $ 115,884 to $ 118,944 and $ 0.88/kWh to $ 0.93/kWh respectively. The variation in NPC and CoE for change in battery cost are shown in Figure 13.

Figure 13 

CoE and NPC analysis of hybrid system with variation in battery cost.

6.4. Variation in bio-gen cost

The net present cost and cost of energy of the hybrid system has been evaluated by variation in bio generator cost. The generator cost has been varied from 0.8 to 1.3 times to its present capital cost. The NPC and CoE of the system varied from $ 115,698 to $ 119,223 and $ 0.88/kWh to $ 0.93/kWh respectively. The variation in NPC and CoE for change in battery cost are shown in Figure 14.

Figure 14 

CoE and NPC analysis of hybrid system with variation in bio-gen cost.

7. Conclusion

In the present study, a hybrid integrated energy system has been investigated using wind turbine, solar PV, and biogas generator as different source component to meet electric load demand. The design, modeling and operation of each system component had been described in detail. The optimization of the integrated system has been optimized by varying the size of the individual components as well as operational strategy. HOMER tool was used to optimize the overall system so as to have maximum renewable energy contribution with minimum net present cost. The most feasible system consists of 12 kW Photovoltaics, 3 kW wind turbine and 15 kW biogas generator with net present cost and cost of energy equal to $ 117,098.1 and $ 0.090/kWh unit respectively. Also, sensitivity analysis of hybrid renewable system has been done with variation in solar PV, wind turbine, battery and biogas generator cost. The IRES generates 71,826 kWh to meet AC load of 64,396 kWh per year. The capacity factor and percentage contribution of PV, wind turbine and biogas generator are 17.8%, 6.57%, 39.1% and 26%, 2.4%, 71.6% respectively. The results show that integrated system is very sensitive with variation in prices of components.